A 15kg of air is supplied per kg of fuel burnt to the combustion chamber of a boiler using fuel 600kg/hr. the temperature of flue gases and ambient air are 273°C and 32°C. If the minimum draught required to start the flue is 9.5mm of water, find out the minimum height of the chimney?
(a) 22.66m
(b) 23.84m
(c) 24.52m
(d) 25.16m
I have been asked this question by my college director while I was bunking the class.
Asked question is from Draught System topic in division Steam Generators & Accessories of Energy Engineering